Document No: LT0122 F3200 Installation & Programming Manual
System Specifications
Issue 2.7 5 July 2001 Page 3-7
3.3.5.2 NDU Quiescent and Alarm Currents
Slimline NDU (FP0714/FP0773/FP0774
4
)
Operating Voltage : 24Vdc (18-28V)
Termination : For up to 2.5sqmm TPS
Quiescent Alarm
Current Consumption : 25mA 80mA
Full cabinet NDU (FP0715)
Quiescent Alarm
Current Consumption (Aust mode)
1
70mA 165mA
Current Consumption (NZ mode)
2
85mA 150mA
1. Includes controller, MAF/PSU, energised standby relay, PA0773 RS485 Bd, LCD
backlight off in quiescent state.
2. Includes controller, MAF/PSU, NZ Display Extender, energised standby and alarm
relays, PA0773 RS485 Bd. LCD backlight off in quiescent state.
3. Refer to Section 3.3.5.1 for additional module currents.
4. For FP0774 the I-Hub currents must be added.